Convert common HVAC engineering units.
Cooling Coil ADP / Bypass Factor Calculator
Estimate apparatus dew point, bypass factor and contact factor from a physically consistent wet-coil cooling/dehumidification process.
Estimate the apparatus dew point and bypass factor of a consistent wet-coil air process.
Explain this screen
Use this when: Reviewing entering and leaving air states for a cooling/dehumidifying coil.
This helps you: Check the idealized process relationship before reviewing coil performance with the supplier.
How to use it
- Choose the temperature unit and the applicable pressure.
- Enter paired dry-bulb and RH readings before the coil.
- Enter paired readings after the coil; review the model result and its limitations.
Before relying on it: The wet-coil straight-process-line model must be physically consistent. This result does not select a coil, predict water temperature or prove manufacturer performance.
Guidance for General
Before you start: Confirm the task, scope, units and source of each value.
Use the result: Check assumptions and applicable criteria before using the result.
Keep the trail: Save useful evidence explicitly and choose the next task when you need it.
Guided and Quick entry use the same engineering engine. These explanations do not change equations, inputs or saved values.
This changes the help on this screen only. Work Mode, permissions, engineering rules and saved values stay under their existing controls.Show example inputs
Learning example only. These values are not measured data or recommended Project criteria.
- Temperature unit
- °C
- Entering air
- 30 °C / 50 % RH
- Leaving air
- 14 °C / 88.1 % RH
- Pressure
- 101.325 kPa absolute (learning assumption)
Local absolute atmospheric pressure, not gauge pressure or sea-level-corrected weather pressure.
Help with barometric pressure
Where to find it: A station-pressure measurement or a documented project pressure basis.
If you don’t know: Psychrometrics can estimate standard atmospheric pressure from altitude and labels it as estimated. Do not treat sea-level starter values as measured site pressure.
Air temperature measured with a dry-bulb sensor.
Help with entering dry-bulb
Where to find it: A suitable temperature instrument or explicitly sourced design air state.
If you don’t know: Obtain a reading for the intended location and operating condition; do not substitute another location's temperature.
Relative humidity of the corresponding air sample, entered as a percentage.
Help with entering rh
Where to find it: A humidity instrument or the approved design air state.
If you don’t know: Measure RH, or use the supported wet-bulb/dew-point input mode in psychrometrics if that measurement is available.
Air temperature measured with a dry-bulb sensor.
Help with leaving dry-bulb
Where to find it: A suitable temperature instrument or explicitly sourced design air state.
If you don’t know: Obtain a reading for the intended location and operating condition; do not substitute another location's temperature.
Relative humidity of the corresponding air sample, entered as a percentage.
Help with leaving rh
Where to find it: A humidity instrument or the approved design air state.
If you don’t know: Measure RH, or use the supported wet-bulb/dew-point input mode in psychrometrics if that measurement is available.
Wet-coil cooling/dehumidification model. The entering and leaving air states must define a physically consistent straight process line that intersects saturation below the leaving state.
What this result means
ADP is the saturation intersection of the modelled air-process line. Bypass factor describes that idealized relationship, not a measured bypass leakage fraction.
Check: The wet-coil straight-process-line model must be physically consistent. This result does not select a coil, predict water temperature or prove manufacturer performance.
Why this result?
The existing engine finds the saturation intersection in dry-bulb/humidity-ratio space and checks the temperature and humidity-ratio bypass factors.
Calculated from the current entered values; these values are not independently verified measurements.
- Entering dry-bulb
- 30 °C
- Entering relative humidity
- 50 %
- Leaving dry-bulb
- 14 °C
- Leaving relative humidity
- 88.1 %
- Barometric pressure
- 101.325 kPa abs
Engineering Method & Assumptions
ADP is solved as the saturation-curve intersection of the straight entering-to-leaving process line in dry-bulb/humidity-ratio space. BF = (T leaving − T ADP)/(T entering − T ADP), with a humidity-ratio BF cross-check. This is not a coil-selection model and does not calculate rows, UA, water temperature, condensate rate, fan heat, or manufacturer performance.
Scope
This is a psychrometric process-line calculation, not a manufacturer coil selection. Verify entering/leaving states, barometric pressure and coil performance against project and manufacturer data.
Useful during psychrometrics & coils work.
- Evaluate moist-air conditions, dew point, condensation risk and cooling/dehumidification processes.
- Check how temperature, humidity and pressure assumptions affect the resulting air state.
- Support coil, cleanroom, comfort and humidity-control discussions with traceable calculations.