Convert common HVAC engineering units.
Dew Point Calculator
Calculate dew point from dry-bulb temperature and relative humidity within the documented range.
Free calculator — authorized account required
Create or sign in to your free professional account. Calculator access is activated only after the applicable Leal approval policy is satisfied; engineering method and reference content remain visible.
Formula / Method
γ = ln(RH/100) + aT/(b+T); Td = bγ/(a−γ)Engineering Method & Assumptions
- Magnus approximation over liquid water; a=17.625, b=243.04 °C.
- Valid only from 0–60 °C and 1–100% RH.
- Not a frost-point calculation.
Applicability: Do not use this Phase 1 method for sub-zero dry-bulb conditions or frost-point determination.
Useful during psychrometrics & coils work.
- Evaluate moist-air conditions, dew point, condensation risk and cooling/dehumidification processes.
- Check how temperature, humidity and pressure assumptions affect the resulting air state.
- Support coil, cleanroom, comfort and humidity-control discussions with traceable calculations.
Frequently asked questions
What is dew point?
Dew point is the temperature at which air reaches saturation when cooled at approximately constant pressure and moisture content.
What happens at 100% RH?
The calculated dew point equals the dry-bulb temperature within numerical tolerance.
Does this tool calculate frost point?
No. It uses an approximation over liquid water and does not calculate frost point.