Convert common HVAC engineering units.
EER / COP / kW per TR Converter
Convert common steady-state HVAC&R efficiency metrics without intermediate rounding.
These are steady-state metric conversions only. They do not calculate seasonal efficiency, IPLV/NPLV, part-load performance, compressor-only efficiency, or equipment rating compliance.
Engineering Method & Assumptions
EER (Btu/Wh) = COP × 3.412141633. kW/TR = 3.5168528420667 ÷ COP. Conversions use International Table BTU and the toolbox refrigeration-ton definition without intermediate rounding.
Scope
This is a metric conversion utility. It does not calculate seasonal or part-load ratings such as IPLV/NPLV and does not determine equipment compliance.