R717 Thermosiphon Oil Cooling
Convert an explicit screw-compressor oil heat load into ammonia thermosiphon circulation, vapor generation, liquid return and added condenser duty—without pretending to size the natural-circulation loop.
Free calculator — authorized account required
Create or sign in to your free professional account. Calculator access is activated only after the applicable Leal approval policy is satisfied; engineering method and reference content remain visible.
Useful during reference & conversion work.
- Resolve unit-system differences quickly across calculations, drawings, schedules and vendor data.
- Look up common formulas, constants and engineering reminders without leaving the HVACR workspace.
- Reduce repeated manual conversion work while keeping the final engineering review with the user.
Frequently asked questions
Does this size a thermosiphon piping loop?
No. It calculates only the R717 heat/mass balance. Natural-circulation driving head, two-phase pressure drop, pipe size, receiver elevation/level and stable circulation require separate engineering.
What return vapor quality should I enter?
Use the applicable OEM or engineered design basis. HVACR Studio intentionally provides no recommended quality or circulation ratio.
Can the oil-cooling duty be calculated from compressor power?
Not by this tool. Oil heat rejection is compressor- and operating-condition-specific. Enter the applicable OEM/design duty or calculate it from explicit oil mass flow, oil specific heat and oil temperature drop.
Does this oil-cooling load affect the condenser?
In the bounded steady-state model, yes. The heat absorbed from the oil returns to the high side and adds the same heat quantity to condenser rejection, neglecting line/environmental heat transfer.